Air Flow Calculator — CFM, Duct Velocity & ACH

HVAC & Engineering Tools

Accurate Air Flow Calculator

Calculate CFM, duct velocity, air changes per hour, heat load, and friction loss - with round, rectangular, and oval duct support in both metric and imperial units.

Inches. Standard round sizes: 4, 6, 8, 10, 12, 14, 16, 18, 20.
Feet per minute (FPM). Typical: 600-900 residential, 1000-1500 commercial.
For total pressure drop estimate.
Air changes per hour. Higher means more ventilation.
BTU/hr. A 2-ton AC equals 24,000 BTU/hr.
Degrees F. Return air minus supply air temperature.
- Result
All Metrics
Practical Guidance
    1,247 people find this calculator useful ❤️

    How to Use This Calculator

    1. Pick your unit system. Imperial (CFM, FPM, inches) for US HVAC work. Metric (m3/h, m/s, mm) for everywhere else.
    2. Choose your tab. Duct Velocity for airflow from velocity and duct size. Air Changes for required CFM from room volume and ACH target. Heat Load for CFM from BTU and temperature difference. Converter for quick unit conversions.
    3. Select duct shape. Round, rectangular, or oval. The calculator computes cross-sectional area automatically.
    4. Enter your figures. Use realistic velocity and ACH values - the hints and reference tables below show typical ranges.
    5. Click Calculate Air Flow. You get primary result, all unit conversions, friction loss estimate, and practical guidance.

    What Makes This Different

    Most air flow calculators handle one equation or one duct shape. This one covers the four calculations HVAC technicians and engineers actually need, with context most tools skip:

    • Four calculators in one. Duct velocity, air changes per hour, heat load, and unit converter - no need to switch tools.
    • Round, rectangular, and oval ducts. Automatic cross-sectional area calculation for all three shapes. Oval uses the flat-oval standard equivalent.
    • Friction loss estimate. Enter duct length and get pressure drop per 100 ft and total pressure loss using ASHRAE-based friction equations.
    • All units shown at once. CFM, m3/h, L/s, FPM, m/s - every conversion visible in the same result card.
    • Real-world ACH targets. Preset dropdown for storage, home, kitchen, commercial kitchen, and cleanroom - with custom option.
    • Fan power estimate. See the approximate watts required to move the air, so you understand the energy cost.
    • Practical guidance. Velocity warnings, recommended ranges, and duct sizing tips tied to your result.
    • Transparent formulas. Every equation documented with its source and assumptions.

    How the Calculation Works

    Air flow calculation reduces to a small set of identities. Everything else is a rearrangement:

    Air Flow (Q) = Velocity (V) x Duct Area (A)
    Air Changes (ACH) = Air Flow (CFM) x 60 / Room Volume (ft3)
    Air Flow (CFM) = Sensible Heat (BTU/hr) / (1.08 x Temperature Difference)
    Friction Loss = 0.109 x (Velocity (FPM) / 1000)^1.9 / Duct Diameter (ft)^1.22

    Step-by-Step Logic

    StepWhat happens
    1Duct dimensions are converted to a cross-sectional area in square feet (imperial) or square metres (metric).
    2Air flow equals velocity x area. Round ducts use pi x r squared. Rectangular use W x H. Oval uses the standard flat-oval equivalent.
    3Flow is converted to all common units: CFM, m3/h, L/s, m3/min.
    4ACH is calculated from CFM and room volume. Or, in reverse, required CFM is calculated from room volume and target ACH.
    5Heat load CFM uses the sensible heat equation with the 1.08 constant (for standard air at sea level).
    6Friction loss is estimated using the ASHRAE-based equation, giving inches of water per 100 ft of duct.
    7Fan power is estimated from flow and total pressure using the fan power equation.

    Duct Area Formulas

    ShapeArea FormulaExample
    RoundA = pi x (D/2)^28 in duct = 0.349 ft2
    RectangularA = W x H12 x 8 in = 96 in2 = 0.667 ft2
    Oval (flat-oval)A = (W - H) x H + pi x (H/2)^212 x 6 in oval = 0.481 ft2

    Reference Tables

    Typical Air Velocity by Application

    ApplicationVelocity (FPM)Velocity (m/s)
    Residential main trunk600 - 9003.0 - 4.6
    Residential branch400 - 6002.0 - 3.0
    Commercial main trunk1000 - 15005.1 - 7.6
    Commercial branch600 - 10003.0 - 5.1
    High-velocity industrial2000 - 250010.2 - 12.7
    Dust collection transport3500 - 450017.8 - 22.9

    Recommended ACH by Space Type

    SpaceACH RangePurpose
    Storage / garage1 - 2Minimal ventilation, odour control
    Standard home / office3 - 5Comfort, humidity, CO2 control
    Kitchen / bathroom5 - 8Moisture, odour, grease removal
    Commercial kitchen8 - 15Heat, smoke, grease extraction
    Laboratory10 - 15Fume control, safety
    Hospital / cleanroom15 - 25Infection control, particulate removal

    Air Flow Unit Conversions

    FromToMultiply By
    CFMm3/h1.699
    CFML/s0.4719
    m3/hCFM0.5886
    m3/hL/s0.2778
    FPMm/s0.00508
    m/sFPM196.85
    in.wgPa249.09
    Pain.wg0.004015

    Worked Examples

    Example 1 - Duct velocity method (8-inch round, 800 FPM)

    StepValue
    Duct diameter8 in = 0.667 ft
    Cross-sectional areapi x (0.333)^2 = 0.349 ft2
    Velocity800 FPM
    Air flow0.349 x 800 = 279 CFM
    In metric279 CFM = 474 m3/h = 132 L/s
    Friction loss (50 ft duct)0.24 in.wg per 100 ft, 0.12 in.wg total

    Example 2 - Room ACH method (20 x 15 x 9 ft room, target 4 ACH)

    StepValue
    Room volume20 x 15 x 9 = 2,700 ft3
    Target ACH4
    Required air flow(2,700 x 4) / 60 = 180 CFM
    In metric180 CFM = 306 m3/h
    Recommended duct size8-inch round at about 660 FPM, or 10 x 6 rectangular

    Example 3 - Heat load method (24,000 BTU/hr, 20 degree delta)

    StepValue
    Sensible heat load24,000 BTU/hr
    Temperature difference20 degrees F
    Required air flow24,000 / (1.08 x 20) = 1,111 CFM
    In metric1,111 CFM = 1,888 m3/h
    This is a 2-ton systemTypical 2-ton AC needs 800-1,200 CFM

    Example 4 - Rectangular duct (12 x 8 inches, 1,000 FPM)

    StepValue
    Width x Height12 x 8 in = 96 in2
    Area in ft296 / 144 = 0.667 ft2
    Velocity1,000 FPM
    Air flow0.667 x 1,000 = 667 CFM
    In metric667 CFM = 1,133 m3/h
    Equivalent roundAbout 11-inch round duct

    Practical Tips

    • Use the right velocity for the job. Residential trunk lines run 600-900 FPM. Branch runs 400-600. Commercial systems run higher. Dust collection needs 3,500+ FPM to keep particles suspended.
    • Check ACH for ventilation. Homes and offices need 3-5 ACH for comfort. Kitchens and bathrooms need 5-8. Commercial kitchens and labs need 8-15. Cleanrooms need 15-25.
    • Match duct size to airflow, not the other way around. Use the ACH method to find required CFM, then size the duct for the correct velocity.
    • Friction loss compounds. Every 100 ft of duct adds pressure drop. Long runs, elbows, and transitions add more. Keep total static pressure within the fan's rating.
    • Altitude matters. The 1.08 constant in the heat load equation assumes sea-level air density. At 5,000 ft, use 1.00. At 8,000 ft, use 0.95.
    • Velocity too high means noise. Above 1,200 FPM in residential systems, you will hear whistling at grilles and dampers. Above 2,000 FPM, noise becomes objectionable in most spaces.
    • Velocity too low means poor distribution. Below 300 FPM, air may stratify and not reach the occupied zone. Below 200 FPM in horizontal runs, dust can settle.
    • Always verify with a balometer. Calculations give you the target. A flow hood or balometer at the grille confirms what is actually happening.

    Frequently Asked Questions

    What is the difference between CFM and FPM?

    CFM (cubic feet per minute) measures volumetric air flow - how much air moves. FPM (feet per minute) measures velocity - how fast it moves. They are related by duct area: CFM equals FPM times area. A large duct can carry the same CFM as a small duct at lower velocity.

    How do I calculate CFM from BTU?

    Use the sensible heat equation: CFM equals BTU/hr divided by (1.08 times temperature difference in F). The 1.08 constant applies at sea level. At altitude, substitute 1.00 for 5,000 ft or 0.95 for 8,000 ft.

    What is a good air velocity in a duct?

    Residential main trunks: 600-900 FPM. Residential branches: 400-600 FPM. Commercial mains: 1,000-1,500 FPM. Below 300 FPM risks poor distribution; above 1,200 FPM in residential causes noise.

    How many air changes per hour does my room need?

    Standard living spaces need 3-5 ACH. Kitchens and bathrooms need 5-8. Commercial kitchens and labs need 8-15. Cleanrooms and hospitals need 15-25. Garages and storage can run 1-2.

    What is the difference between round, rectangular, and oval ducts?

    Round ducts have the lowest friction for a given cross-sectional area and are preferred where space allows. Rectangular ducts fit in tight spaces like wall cavities and above ceilings. Oval (flat-oval) ducts are a compromise - they fit in shallow spaces but have higher friction than round.

    How do I convert between CFM and m3/h?

    Multiply CFM by 1.699 to get m3/h. Multiply m3/h by 0.5886 to get CFM. The Converter tab handles this automatically for flow, velocity, dimensions, and pressure.

    What is friction loss and why does it matter?

    Friction loss is the pressure drop as air moves through ductwork. Every foot of duct, every elbow, and every transition adds resistance. If total friction loss exceeds the fan's static pressure rating, airflow drops. This calculator estimates friction loss per 100 ft using ASHRAE-based equations.

    Does altitude affect airflow calculations?

    Yes. Air density decreases with altitude, so the same fan moves less mass of air at higher elevations. The heat load equation uses a 1.08 constant at sea level. At 5,000 ft, use 1.00. At 8,000 ft, use 0.95. Velocity-based calculations are less affected because they measure volume, not mass.

    What size duct do I need for 1,000 CFM?

    It depends on target velocity. At 800 FPM, you need 1.25 ft2 of area - a 12-inch round duct (0.785 ft2) would run at about 1,274 FPM, too high for residential. Use a 14-inch round (1.07 ft2) for about 935 FPM, or a 16-inch round (1.40 ft2) for about 714 FPM. The Duct Velocity tab calculates this for you.

    References & Methodology

    1. ASHRAE Handbook - Fundamentals. Duct Design. American Society of Heating, Refrigerating and Air-Conditioning Engineers, current edition.
    2. ASHRAE Standard 62.1. Ventilation for Acceptable Indoor Air Quality. American Society of Heating, Refrigerating and Air-Conditioning Engineers.
    3. SMACNA. HVAC Duct Construction Standards - Metal and Flexible. Sheet Metal and Air Conditioning Contractors' National Association.
    4. BAPI. Determining Duct Air Flow in CFM using the BAPI Pressure Sensor. Application Note, 2015.
    5. TSI Incorporated. Flow Rate Calculations. TSI Application Note.
    6. Engineering Toolbox. Duct Velocity. engineeringtoolbox.com, 2005.
    7. ACCAdemic. Airflow and CFM Air Exchange Calculator. protoolreviews.com, 2026.
    8. Angi. How to Calculate CFM. angi.com, 2025.
    9. NY Engineers. What Is CFM in HVAC and How to Calculate It. ny-engineers.com, 2025.
    © 2026 all rights reserved
    ComfortSkillz Blog